» Redressor TestIng System
+90 0850 441 0591
entrdeares
Our Social Media Accounts

Redressor TestIng System

Redressor TestIng System

Redressor Testing System
Testing Battery Redressor Systems
 Redressor Testing Systems are using produced redressor system’s full load test, load strengh test and discharge tests.

 

General
  • The desired current can be apply at wide voltage values.
  • Can test on the computer according to pre-test scenarios.
  • Easy to use. With two cable connections you can start testing immediately. Qualified personnel will remove the need.
  • You can get test parameters as test report.
  • One-touch testing with automatic mode
  • Test possibility by setting current-voltage lower / upper values and duration with manual mode
APPLICATIONS
  • UPS, Battery Redressor Testing
TECHNICAL SPECIFICATIONS
  • Working Voltage                 : 24-48Vdc / 110-220Vdc %30+- (16,8Vdc to 286Vdc)
  • Nominal Current               : 255A
  • Maximum Current            : 330A
  • Resolution                          : 5A, optinal 1A
  • Load Measuremenr Er*   : %10
  • Load Control                      : Automatic Contactor with computer control and manual
  • Supply Voltage                   : 220Vac external supply
  • Input Terminal                   : Socket or Busbar
  • Meters                                 : Current, Voltage
  • Over Current Portection  : Yes
  • Over Voltage Protection  : Yes
  • Emergency Stop                : Yes
  • Control Computer            : Control Computer, Display, Wireless Controller,  Control Software, USB Output, Emergency Stop, Manual Control Switchs.

STANDARTS:
IEEE 32, IEC60137,  EN10346, ISO129 44, IEC60071, IEC60060, IEC60529,IEC60273, ISO-EN 1461,

USER MANUAL